Heat pump sizing: how many kW your house needs

The “100 W per m²” rule ignores your climate and insulation. Here is the output your house needs during the coldest days where you live.

A heat pump’s output is chosen to cover the house’s heat losses when it is coldest. It is worked out from the home’s heat-loss coefficient (G, in watts per cubic metre per degree of difference), the heated volume and the gap between 19 °C indoors and the reference outdoor temperature. The site takes as its reference cold the average of the three coldest consecutive days of each winter, measured by Météo-France from 2015 to 2024 at the station of the département’s main town: 5.2 °C in the Alpes-Maritimes, -2.7 °C in the Doubs. An average 100 m² house then needs 3.8 kW in Nice and 6.0 kW in Besançon. This is an order of magnitude: the installer sizes with the standard’s design temperature, which is lower, and must give you a heat-loss study. An oversized heat pump costs more and wears out cycling on and off; an undersized one leaves the backup heater doing the work.

What heat pump output do I need?

Output needed in cold spells

7.3 kW

3 coldest days (Strasbourg - Botanique)-3.2 °C
Heated volume300 m³
Air-to-water price guide (median per kW)€12,432

Estimate: assumed ceiling height 2.5 m, the site’s insulation coefficient, 19 °C set point; the installer sizes with the standard design temperature, which is lower.

Add the price and grants →

Checked by Radif Partners · Editorial policy · Method and sources

The calculation, step by step

The output needed equals G × volume × (19 °C − reference cold). Volume is the heated floor area times the ceiling height, 2.5 m by default. The G coefficient sums up insulation: it is how many watts each cubic metre loses per degree of difference between inside and outside. The site uses four usual values:

The site’s working assumptions (usual orders of magnitude), changed in the calculator by the insulation choice
InsulationG coefficient (W/m³·°C)Example
Poorly insulated1.60Pre-1975 house never renovated
Average1.10Insulated loft, double glazing
Well insulated0.75Walls, loft and windows renovated
Low-energy0.50Low-energy building, RT 2012

These coefficients are assumptions, not measurements of your house. The only way to get the real figure is a room-by-room heat-loss study, which the installer should carry out before proposing an output. If your quote states an output with no calculation at all, ask for it.

Output by département

The reference cold varies a lot between départements, and the output with it. For a 100 m² house:

100 m² house, 2.5 m ceilings, 19 °C indoors; typical cold = average of each winter’s 3 coldest consecutive days, Météo-France 2015-2024
DépartementTypical coldPoorly insulatedAverageWell insulatedLow-energy
Alpes-Maritimes (06)5.2 °C5.5 kW3.8 kW2.6 kW1.7 kW
Gironde (33)2.0 °C6.8 kW4.7 kW3.2 kW2.1 kW
Paris (75)-0.1 °C7.6 kW5.3 kW3.6 kW2.4 kW
Rhône (69)-1.1 °C8.0 kW5.5 kW3.8 kW2.5 kW
Cantal (15)-2.3 °C8.5 kW5.9 kW4.0 kW2.7 kW
Doubs (25)-2.7 °C8.7 kW6.0 kW4.1 kW2.7 kW
Bas-Rhin (67)-3.2 °C8.9 kW6.1 kW4.2 kW2.8 kW

The seven départements in the table run from mildest to harshest. All 96 mainland départements, with their station and typical cold, are on the heat pump by département page.

Output and price

A heat pump’s price depends first on its output. Across the 22 air-to-water quotes published by the price observatory in 2026, the median is €1,697 per kW installed; across the 148 air-to-air quotes, €1,030 per kW. An average 100 m² house in the Rhône, at 5.5 kW, therefore comes to about €9,380 for air-to-water at that median price, an estimate to compare with your quotes. The air-to-water sample is small: the real range is wide.

What heat pump output do I need?

Output needed in cold spells

7.3 kW

3 coldest days (Strasbourg - Botanique)-3.2 °C
Heated volume300 m³
Air-to-water price guide (median per kW)€12,432

Estimate: assumed ceiling height 2.5 m, the site’s insulation coefficient, 19 °C set point; the installer sizes with the standard design temperature, which is lower.

Add the price and grants →

Output and consumption are not the same thing

Output (in kW) is what the heat pump must deliver at the worst moment of winter; consumption (in kWh per year) is what it uses over the whole season. A house may need 8 kW in a hard frost yet use only 4,000 kWh of electricity over the year, because most days are much milder. Consumption is worked out with degree-days, explained on the climate and degree-days page, and costed on the heat pump running cost page.

Insulate before changing your heating

Going from a poorly insulated to a well insulated house more than halves the output needed. If you plan to insulate the loft or replace windows in the coming years, do it first: you will buy a smaller, cheaper heat pump that runs in better conditions. MaPrimeRénov’ also funds insulation work, per item or within a whole-home renovation.

Frequently asked questions

What size heat pump for 100 m²?

For an averagely insulated 100 m² house, the site’s calculation gives from 3.8 kW on the Riviera to 6.0 kW in the Doubs, during the three coldest days of a typical winter. A poorly insulated house needs about 45% more, a low-energy house half as much. The installer adds a margin for severe frosts.

Should I buy a more powerful heat pump to be safe?

No. An oversized heat pump costs more to buy, starts and stops constantly in spring and autumn, which wears the compressor and lowers efficiency. It is usually sized to cover 80 to 100% of needs at the design temperature, with a backup heater taking over on the few coldest days of the year.

How does the site’s typical cold differ from the design temperature?

The design temperature of standard NF EN 12831 is an extreme cold, around −5 to −15 °C depending on zone and altitude, which installers use for sizing. Lacking an open table, the site measures each winter’s typical cold from Météo-France records. It therefore gives a lower output, useful for judging a quote, not for replacing the study.